Installation and Operation Manual
●
Fan Coil Controller – EZstat
EC-EZstat
Date: 9-2014 Supersedes: NEW
Engineered Comfort reserves the right to change any information concerning product or specification without notice or obligation.
Page 16 of 36
6.1 Createand/orChangePasswords
For access to the commissioning funcons you will need to know the Admin Level Password, also known as Password 2.
If the controller has not been previously set up, no password is required and the user can either connue on to setup the
User & Admin Level passwords (see table below) or proceed directly to the secon of interest.
PasswordFuncons:
• User Level – Calls up Password 1 in the program. This is for a facility user and limits changes to acve setpoints, fan
operaon, occupancy, and heang and cooling modes.
• Admin Level – Calls up Password 2 in the program. This is generally used by a controls technician to set up and
commission the EZstat. When set, will lock user out from setpoints, fan operaon, occupancy, and heang and
cooling modes.
Procedure Steps Display
Starng
Display
Start at the temperature display.
F
°
AUTO AUTO
Creang
Password 1
1. Press the le and right buons below the display at the same me and
hold them unl the display changes to the SECURITY ADMIN LEVEL display
2. If Password 2 has not previously been entered, the display
will change to the MAIN menu. Otherwise, enter the password.
3. Under the MAIN menu, select ADVANCED followed by PASSWORDS.
4. Select the password you wish to congure and proceed to the next
screen.
5. Press either the or buon to program the rst digit of
Password 1 and/or Password 2.
6. Press the Enter buon to select the next digit.
7. Repeat steps 5 & 6 for all remaining digits.
Enter
ADMIN LEVEL
0 0 0 0
Enter
SETPOINT
SCHEDULE
SYSTEM
COMM
ADVANCED
Enter
PASSWORD1:
0 0 0 0