Engineered Comfort Fan Coil Controller EZstat Specifikace Strana 32

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 36
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 31
Installation and Operation Manual
Fan Coil Controller – EZstat
EC-EZstat
Date: 9-2014 Supersedes: NEW
Engineered Comfort reserves the right to change any information concerning product or specification without notice or obligation.
Page 32 of 36
Temperature points—the following analog value objects represent temperatures points derived from the EZstat input
sensors.
Table8–5 Analogvalueobjects—Temperaturepoints
Value object Name Descripon
AV1 SPACE_TEMP Space Temperature
AV19 WATER_TEMP Water Temperature
AV20 DISCHARGE_TEMP Discharge Air Temperature
Value objects
BACnet value objects represent setpoints or other operaonal data in the EZstat.
Setpoints—the analog value objects in the following table represent operaonal setpoints for the EZstat applicaons. All
of the setpoints are available from the user interface.
Value object Name Descripon
AV3 ACT_COOL_STPT Acve Cooling Setpoint
AV4 ACT_HEAT_STPT Acve Heang Setpoint
AV5 OCC_CL_STPT Occupied Cooling Setpoint
AV6 OCC_HT_STPT Occupied Heang Setpoint
AV7 UNOCC_CL_STPT Unoccupied Cooling Setpoint
AV8 UNOCC_HT_STPT Unoccupied Heang Setpoint
AV9 MAX_CL_STPT Minimum Cooling Setpoint
AV10 MAX_HT_STPT Maximum Heang Setpoint
AV11 MIN_STPT_DIFF Minimum Setpoint Dierenal
AV12 STBY_OFFSET Standby Oset
AV25 FAN_OFF_DELAY Fan O Delay
AV31 Max_VLV_LOW Maximum Valve at Low Fan Speed
AV32 Max_VLV_MED Maximum Valve at Medium Fan Speed
AV33 Max_VLV_HIGH Maximum Valve at High Fan Speed
AV34 FAN_SPEED Fan Speed
AV35 FAN_COOL_MAX Fan Cool Maximum Speed
AV36 FAN_MINIMUM Fan Minimum Speed
AV37 FAN_HEAT_MAX Fan Heat Maximum Speed
AV38 OVRD_TIME Local Override Timer
Table8–4 Analogvalueobjects—Setpoints