Installation and Operation Manual
Fan Coil Controller – EZstat
EC-EZstat
Date: 9-2014 Supersedes: NEW
Engineered Comfort reserves the right to change any information concerning product or specification without notice or obligation.
Page 18 of 36
6.3 Setupthecommunicaons
Seng BACnet communicaons properes is required only if the EZstat is integrated into a network with other BACnet
controllers. Entering the communicaons properes requires entering Password 2.
See the topic Connecng to MS/TP network for network wiring details.
Procedure Steps Display
Starng Display
1. Start at the temperature display.
2. Enter Password 2. The display changes to the MAIN menu display.
F
°
70
AUTO AUTO
Enter
SECURITY
ADMIN LEVEL
0 0 0 0
Change the
network
communicaon
properes.
1. From the MAIN menu, press either the or buon to select COMM.
2. Press Enter. The COMM menu opens.
3. Choose and set the following properes:
DEVICE ID—This is the BACnet device instance. The device instance
must be within the range of 1 to 4,194,302.
MAC—The MAC address must be in the range of 1‑127.
BAUD—Set to match other devices on the BACnet MS/TP network.
The choices are Auto, 9600, 19,200, 38,400, or 76,800.
Note: Aer changing a communicaon property, the EZstat will reset.












Back
Enter
DEVICE ID:
0000000


 





NOTE