Installation and Operation Manual
Fan Coil Controller – EZstat
EC-EZstat
Date: 9-2014 Supersedes: NEW
Engineered Comfort reserves the right to change any information concerning product or specification without notice or obligation.
Page 22 of 36
Procedure Steps Display
Choose and
set the fan coil
system opons
3. Press the to choose any of the following items:
BackEnterExit
SYSTEM
STAGE 1 FAN
STAGE 2 FAN
MAX VLV LOW
MAX VLV MED
MAX VLV HIGH
DAT ENABLE
VLV ACTION
Common Opons Two Pipe Only
LOCAL OVRD TIME
FAN OFF DELAY
OCCUPIED FAN
FAN SPEEDS (three speed fans only)
FAN COOL MAX
FAN MINIMUM (modulang fans only)
FAN HEAT MAX
MOD FAN ACTION
MAX VLV LOW
MAX VLV MED
MAX VLV HIGH
DAT ENABLE
AUTO FAN RESET
STAGE 1 FAN
STAGE 2 FAN
VLV ACTION
Four Pipe Only
CL VLV ACTION
HT VLV ACTION
Set the local
override me.
Set the local override me. From the SYSTEM menu choose LOCAL OVRD
TIME to set the me the EZstat will hold an override temperature setpoint
as the acve setpoint. At the end of the period, the EZstat will use either
an occupied or unoccupied setpoint as the acve setpoint.



Set the fan
delay.
From the SYSTEM menu choose FAN DELAY
OFF to set the me the system fan will connue to run aer the last heat
ing or cooling stage is turned o.



Set the
occupied fan
control.
From the SYSTEM menu choose OCCUPIED FAN to choose the following:
When ON, the fan will run connuously when the schedule is
occupied (On).
When the schedule is unoccupied (O) the fan will run only when
there is a call for heang or cooling.




Set fan speeds
for three‑
speed fans.
Select FAN SPEEDS from the SYSTEM menu to designate the number of
speeds at which the installed fan will run.





Set fan speeds
for modulang
speed fans
Select FAN MINIMUM and FAN MAXIMUM from the SYSTEM menu to set
fan speed for modulaon fans.
FAN MINIMUM—Sets the slowest speed at which the fan will run
when a user sets the fan speed to LOW.
FAN HEAT MAXIMUM—Sets the fastest speed at which the fan will
run when a user sets the fan speed to HIGH for heang.
FAN COOL MAXIMUM – Sets the fastest speed at which the fan will
run when a user sets the fan speed too HIGH for cooling.
The Min. and Max. CFMs are also the range at which the ECM operates
throughout the sequence when set to auto.
Enter
FAN MINIMUM
25%
Enter
FAN HEAT MAX
100%
Enter
FAN COOL MAX
100%
NOTE